16 Entek 9000 Series Sensor Installation Guide
Connecting 9000 Series Sensors to Monitors
Common
Channel A Signal
Pin A - Signal
Pin B - Common
Cable shield not
connected at this end
Note: If shield is connected at the transducer, do not
ground the shield at the 5800 monitor end. If shield
connection is unknown at the two pin connector,
ohm out and verify before wiring.
1 SIG AND +24 VDC
2
3 SIG GND COMMON
4
5
6 0-5 VDC RECORDER CHAN A
7 GND
8 4-20 MA CURRENT TRANSMITTER CHAN A
9 -24 VDC
10 ANALYZER CHAN A
1 ANALYZER CHAN B
2 +24 VDC
3 4-20 MA CURRENT TRANSMITTER CHAN B
4 GND
5 0-5 VDC RECORDER CHAN B
6
7
8 SIG GND COMMON
9
10 SIG AND +24 VCD
Pin A - Signal
Pin B - Common
Shield
Common
Channel B Signal
Shield
Cable shield not
connected at this end
CONNECTING 9000 SERIES TRANSDUCERS TO A 5800 MONITOR
This shows a dual-channel card. For single-channel
card, only wire in top channel