Seitenansicht 14
Commands Reference
CoolMaster PRM
15
www.coolautomation.com
© 2011 Cool Automation LTD
Rev 3.8
without connecting CoolMaster to Air Conditioning system line. To exit simulation mode set N to zero or
restart CoolMaster.
EXAMPLE
>simul 20
OK
Simulate 20 Indoor Units
>simul 0
OK
Terminate simulation mode
EXIT CODE
OK
Request Successfully Executed
4.1.15 stat
SYNOPSIS
stat [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units
EXAMPLE
>stat
100 ON 12C 12,41C High Cool OK
101 OFF 32C 04,93C Low Dry OK
102 ON 07C 08,27C High Dry OK
103 OFF 01C 26,84C Med Dry OK
104 ON 04C 24,08C High Dry OK
105 OFF 11C 07,23C Low Dry OK
106 ON 11C 14,91C Auto Dry OK
107 ON 27C 12,94C Med Cool OK
OK
>stat 101
101 OFF 32C 04,93C Low Dry OK
OK
RESPONSE
Position in String
Example
Format
Description
0-2
109
NNN
Indoor unit Centralized Address
4-6
ON
ON or OFF
On/Off Status
8-10
23C
NNC
Set Temperature ºC
12-17
24,08C
NN,NNC
Room Temperature ºC
19-22
Auto
Low,Med,High,Auto,Top
Fan Speed
24-27
Cool
Cool,Heat,Fan,Dry,Auto
Auto,Bps,HExc*
AutC,AutH**
Operation Mode
29-32
OK
OK or Xn, Xnn, nnnn
OK or Failure code
* - See vam command
** - See auto command