Cool Automation CoolMaster 3000T Bedienungsanleitung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 19
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
Commands Reference
CoolMaster PRM
13
www.xdimax.com
© 2009 XDIMAX LTD
Rev 3.0
3.1.14 stat
SYNOPSIS
stat [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units
EXAMPLE
>stat
100 ON 12C 12,41C High Cool OK
101 OFF 32C 04,93C Low Dry OK
102 ON 07C 08,27C High Dry OK
103 OFF 01C 26,84C Med Dry OK
104 ON 04C 24,08C High Dry OK
105 OFF 11C 07,23C Low Dry OK
106 ON 11C 14,91C Auto Dry OK
107 ON 27C 12,94C Med Cool OK
OK
>stat 101
101 OFF 32C 04,93C Low Dry OK
OK
RESPONSE
Position in String
Example
Format
Description
0-2
109
NNN
Indoor unit Centralized Address
4-6
ON
ON or OFF
On/Off Status
8-10
23C
NNC
Set Temperature ºC
12-17
24,08C
NN,NNC
Room Temperature ºC
20-23
Auto
Low or Med or High or Auto
Fan Speed
25-28
Cool
Cool or Heat or Fan or Dry
Operation Mode
30-32
OK
OK or XN
OK or Failure code
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
v 0.0.1
CoolMaster 2000S
v 2.0.9
This command is obsolete and is supported only for backward compatibility.
3.1.15 stat2
SYNOPSIS
stat2 [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units. stat2 compared to stat1 has additional Filter Reset
Sign indication